| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allow user-assisted remote attackers to execute arbitrary code via a crafted project file, related to the HMI web server and runtime loader. |
| The TELNET daemon in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime does not perform authentication, which makes it easier for remote attackers to obtain access via a TCP session. |
| Stack-based buffer overflow in HmiLoad in the runtime loader in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime, when Transfer Mode is enabled, allows remote attackers to execute arbitrary code via vectors related to Unicode strings. |
| Directory traversal vulnerability in HmiLoad in the runtime loader in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime, when Transfer Mode is enabled, allows remote attackers to execute, read, create, modify, or delete arbitrary files via a .. (dot dot) in a string. |
| HmiLoad in the runtime loader in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime, when Transfer Mode is enabled, allows remote attackers to cause a denial of service (application crash) by sending crafted data over TCP. |
| Siemens Simatic WinCC and PCS 7 SCADA system uses a hard-coded password, which allows local users to access a back-end database and gain privileges, as demonstrated in the wild in July 2010 by the Stuxnet worm, a different vulnerability than CVE-2010-2568. |
| Siemens SIMATIC S7-1200 PLCs 2.x and 3.x allow remote attackers to cause a denial of service (defect-mode transition and control outage) via crafted packets to TCP port 102 (aka the ISO-TSAP port). |
| Directory traversal vulnerability in miniweb.exe in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allows remote attackers to read arbitrary files via a ..%5c (dot dot backslash) in a URI. |
| miniweb.exe in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime does not properly handle URIs beginning with a 0xfa character, which allows remote attackers to read data from arbitrary memory locations or cause a denial of service (application crash) via a crafted POST request. |
| Untrusted search path vulnerability in Siemens SIMATIC STEP7 before 5.5 SP1, as used in SIMATIC PCS7 7.1 SP3 and earlier and other products, allows local users to gain privileges via a Trojan horse DLL in a STEP7 project folder. |
| Siemens SIMATIC S7-400 PN CPU devices with firmware 6 before 6.0.3 allow remote attackers to cause a denial of service (defect-mode transition and service outage) via crafted ICMP packets. |
| Siemens SIMATIC S7-400 PN CPU devices with firmware 5.x allow remote attackers to cause a denial of service (defect-mode transition and service outage) via (1) malformed HTTP traffic or (2) malformed IP packets. |
| Siemens SIMATIC WinCC OA before 3.12 P002 January allows remote attackers to cause a denial of service (monitoring-service outage) via malformed HTTP requests to port 4999. |
| Directory traversal vulnerability in Siemens SIMATIC WinCC OA before 3.12 P002 January allows remote attackers to read arbitrary files via crafted packets to TCP port 4999. |
| The integrated web server in Siemens SIMATIC WinCC OA before 3.12 P002 January allows remote attackers to execute arbitrary code via crafted packets to TCP port 4999. |
| Cross-site request forgery (CSRF) vulnerability in WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, allows remote attackers to hijack the authentication of arbitrary users for requests that modify data or cause a denial of service. |
| WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, stores sensitive information under the web root with insufficient access control, which allows remote attackers to read a (1) log file or (2) configuration file via a direct request. |
| Affected devices do not contain an Immutable Root of Trust in Hardware. With this the integrity of the code executed on the device can not be validated during load-time. An attacker with physical access to the device could use this to replace the boot image of the device and execute arbitrary code. |
| Insufficient control flow management in subsystem for Intel(R) CSME versions before 11.8.80, 11.12.80, 11.22.80, 12.0.70, 13.0.40, 13.30.10, 14.0.45 and 14.5.25 , Intel(R) TXE versions before 3.1.80 and 4.0.30 may allow an unauthenticated user to potentially enable escalation of privilege via physical access. |
| A vulnerability has been identified in SIMATIC PCS neo (Administration Console) V4.0 (All versions), SIMATIC PCS neo (Administration Console) V4.0 Update 1 (All versions). The affected application leaks Windows admin credentials. An attacker with local access to the Administration Console could get the credentials, and impersonate the admin user, thereby gaining admin access to other Windows systems. |